The Schneider Electric METSEPM3255 PowerLogic PM3255 is a multifunction power meter for electrical installation monitoring, energy measurement, and network supervision. Designed for DIN rail mounting, it measures voltage, current, frequency, active, reactive and apparent power, power factor, energy, and harmonic distortion, and also offers RS485 Modbus communication, data logging, multi-tariff management, 2 digital inputs, and 2 digital outputs.
The PM3255 uses current inputs of 1 A or 5 A via external current transformers and provides an accuracy of Class 0.5S for active energy according to IEC 62053-22. Its backlit graphical LCD display makes it easy to view electrical parameters locally, while the RS485 port allows the meter to be integrated into supervision, automation, and energy management systems.
The PowerLogic PM3255 allows you to centralize the main variables needed to understand the behavior of an electrical installation in a single device.
These features make the PM3255 suitable both for network monitoring and for consumption tracking, internal cost allocation, and analysis of the energy behavior of installations.
One of the standout features of the METSEPM3255 is its accuracy for active energy measurement. Schneider Electric specifies a Class 0.5S in accordance with IEC 62053-22, suitable for applications where precise energy measurement is required.
QuantityClass / accuracyActive energyClass 0.5S according to IEC 62053-22Active energyClass 1 according to IEC 62053-21Reactive energyClass 2 according to IEC 62053-23Voltage±0.3%The PM3255 does not directly measure high installation currents. Its inputs are designed to work with current transformers with a secondary of 1 A or 5 A.
This makes it possible to adapt the meter to installations with very different current levels by selecting the appropriate current transformers and configuring the transformation ratio in the device.
Current characteristicValueCompatible transformer secondary1 A / 5 AConfigurable primary1-32767 AMeasurement range with CT x/5 A0.05-6 AMeasurement range with CT x/1 A0.02-1.2 AThe current transformer ratio must be programmed correctly so that the readings displayed and logged by the meter correspond to the actual installation values.
The PM3255 can directly measure voltages within the ranges supported by the manufacturer and can also operate with voltage transformers when the application requires it.
Measurement typeRangePhase-neutral50-330 V ACPhase-phase80-570 V ACMeasurement frequency45-65 HzWith external voltage transformerUp to 999,000 V AC configurableThanks to the use of suitable voltage and current transformers, the PowerLogic PM3200 family can be integrated in both low-voltage applications and higher-voltage systems that require external instrumentation.
In addition to energy consumption, the PM3255 measures the three fundamental electrical power quantities: active, reactive, and apparent. Values can be viewed for the entire installation or individually by phase.
This information makes it easier to assess electrical load and helps identify operating conditions that may affect the installation’s energy performance.
The meter calculates the total and per-phase power factor. This quantity helps assess the relationship between the active power actually used and the apparent power drawn from the grid.
Monitoring it can be useful for detecting installations with a high level of reactive energy and evaluating possible compensation measures.
The PowerLogic PM3255 records active, reactive, and apparent energy, including import and export values.
This capability is especially useful in bidirectional installations or systems where it is important to separately track energy consumed and energy delivered to the grid or to other circuits.
The device calculates demand values for current and active, reactive, and apparent power. In addition to present demand, it allows maximum demand values to be recorded.
Demand analysis makes it easier to identify consumption peaks and can help optimize installation sizing, electricity contracting, and load management.
The PM3255 includes basic network quality analysis functions, including measurement of total harmonic distortion THD of voltage and current.
It also allows harmonic components up to the 15th harmonic to be analyzed, providing useful information for detecting waveform distortion associated with electronic loads, variable speed drives, switched-mode power supplies, and other non-linear equipment.
The meter uses an acquisition rate of 32 samples per cycle. This sampling capability is part of the PM3200 range measurement architecture and allows the RMS values and energy indicators used by the device to be obtained.
The METSEPM3255 is the most complete version of the PM3200 range in terms of information storage. It has 512 kB of internal memory and can log different variables for later analysis.
The PM3255 allows you to configure up to 15 time-stamped alarms. This function makes it easier to automatically monitor certain electrical conditions without constantly checking the values shown on the display.
The digital outputs can be used in certain configurations to signal alarm states to other systems or equipment.
The device includes a real-time clock that provides the time reference needed for functions such as event logging, historical records, and multi-tariff management.
The time stamp makes it easier to identify the exact moment when an alarm or a specific energy event occurred.
The Schneider Electric PM3255 supports energy accumulation in up to 4 different tariffs. Tariff selection can be made via:
This feature allows consumption to be separated by time bands, tariff periods, or operating states according to the installation strategy.
The METSEPM3255 reference includes 2 digital inputs. These inputs allow information from external devices to be received and used within the meter’s available functions.
Possible uses include external tariff control, monitoring equipment status, or collecting certain field signals.
FeatureValueNumber of digital inputs2Rated voltage24 V DCRange11-40 V DCMaximum consumption≤4 mAThe PM3255 also includes 2 solid-state digital outputs, identified as DO1 and DO2.
The outputs can be configured for different functions:
DO1 can be used for active energy pulses and DO2 for reactive energy pulses, according to the device configuration.
Output featureValueNumber of outputs2TechnologySolid-state relayVoltage range5-40 VMaximum current50 mAThe meter includes an RS485 port for integration into supervision and automation networks using the Modbus protocol.
Communication allows remote consultation of measurements, statuses, and records, and integration of the PM3255 into energy management systems, PLCs, gateways, and compatible BMS platforms.
CommunicationSpecificationPhysical interfaceRS485, 2-wireProtocolsModbus RTU / ASCIISpeed9.6-38.4 kbaudThe PM3255 features a backlit 128 x 96-pixel graphical LCD display, designed to make data easy to read directly from the front of the panel.
The front buttons allow you to navigate through the different menus, view values, access historical data, and modify authorized configuration parameters.
The front panel includes an energy pulse LED with an indicated constant of 5,000 pulses/kWh. This indicator provides a visual reference during operation and device verification tasks.
The control power supply supports different ranges, making installation easier in panels with different available voltages.
Power typeRangeAC phase-neutral100-277 V ACAC phase-phase173-480 V ACDC100-300 V DCAC frequency45-65 HzSchneider Electric specifies a reference consumption of approximately 3 W / 5 VA on AC power supply.
The PowerLogic PM3255 is designed for clip-on DIN rail mounting. Its width is approximately 90 mm, equivalent to 5 modules of 18 mm, allowing it to be neatly integrated into distribution panels.
DimensionValueWidth90 mmHeight95 mm approx.Depth70 mmModule width5 modules of 18 mmNet weight0.26 kg approx.The meter has an IP40 protection rating on the front panel and IP20 on the body in accordance with IEC 60529.
It is designed for installation inside electrical panels or suitable enclosures that provide the environmental protection level required by the application.
The PM3255 is designed to operate in a wide range of conditions typical of professional electrical panels.
ConditionValueOperating temperature-25 to +70 °CStorage temperature-40 to +85 °CRelative humidity5-95%Operating altitudeUp to 3,000 mPollution degree2Thanks to its combination of measurement, communications, logging, and inputs/outputs, the PM3255 can be used in many electrical and energy environments.
The METSEPM3255 reference has 1 A/5 A current inputs and is not designed to connect directly to the main currents of a high-current installation.
To perform the measurement, compatible current transformers with a 1 A or 5 A secondary and a primary ratio suitable for the circuit current must be selected. The transformation ratio must then be configured in the PM3255.
The Schneider Electric PowerLogic PM3255 METSEPM3255 is a compact, complete power meter for installations that require energy monitoring and electrical supervision. Its Class 0.5S accuracy, multifunction measurement, THD and harmonic analysis, 4 tariffs, 15 alarms, internal memory, digital inputs and outputs, and RS485 Modbus communication make it an especially suitable solution for professional electrical panels and energy management systems.